Banner

news

Home>news>Content

Precautions for the installation of high temperature resistant centrifugal fans

2019-05-16

Hebei Shunteng Fan Manufacturing Co., Ltd. is located in Gaobeidian City, Hebei Province. It is a professional manufacturer engaged in fan manufacturing. The products are exported to countries in Asia, Europe and America, and are well received by users and enjoy a high reputation at home and abroad. The factory produces various types of high, medium and low pressure centrifugal and axial fans, boiler drums, induced draft fans, and low-noise multi-stage centrifugal blowers. The following editor will introduce to youHigh temperature resistant centrifugal fanInstallation considerations.

1.High temperature resistant centrifugal fanVentilation should be arranged on the floor or platform as much as possible for maintenance and repair; when the centrifugal fan is equipped with a motor power less than or equal to 75kW, it is not necessary to install a valve for starting only. When a centrifugal boiler induced draft fan is selected for discharging high temperature flue gas or air, a valve for starting should be installed to prevent the motor from overloading during cold operation.
2.High temperature resistant centrifugal fanThe installation pedestal should have sufficient strength, stability and durability, and the vibration of the pedestal should meet the following requirements:
1) The natural vibration frequency of the basic device shall not be greater than 1/3 of the rotational speed of the motor and fan.
2)High temperature resistant centrifugal fanThe difference between the vibration speed during operation and the vibration speed when the fan is stationary must be more than 3 times.
3.High temperature resistant centrifugal fanThe connection between the inlet and outlet and the air pipe shall be provided with a flexible joint. The air inlet pipe, air outlet pipe and other devices should be independently supported and firmly supported by the foundation or other components of the building. The casing should not bear the weight of other parts.
4.High temperature resistant centrifugal fanWhen installed on building components, vibration isolation measures should be taken.

The above is all the content that the editor brings to you today. We mainly sell in Hebei, Northeast, Henan, Tianjin, Shaanxi, Inner Mongolia, Shanxi, and Ningxia. Our company always adheres to: "Systematic management, high-quality products, and intentions With the business philosophy of "good service and honesty as the foundation", we are willing to provide new and old customers with better products and preferential prices to achieve continuous improvement and development of the enterprise. We hope that we can cooperate with you in the future to create a win-win situation!


Maintenance of anticorrosive centrifugal fan and the cause of failure

High-pressure blower manufacturer's introduction to the components of the fan